Generator size calculator
List the equipment you need to power. The calculator estimates the generator size in kVA and shows the catalog models that cover it.
- Generator models to match
- 61
- Engine brands
- 4
- Prime power range (kVA)
- 11–1,710
Your equipment
Enter the power printed on each item's nameplate or datasheet.
Add a common load
How the generator will be used
This is an estimate
The result follows common sizing rules, not a site survey. Motor starting, power quality and site conditions change the final size, so confirm it with a Mega Power engineer before you order.
Ask for a load studyHow the estimate works
- Running load: each item's power multiplied by its quantity, added together. 1 HP is counted as 0.746 kW.
- Motors draw extra power while starting: about 3 times their running power when started directly, 2 times with a soft starter or star-delta, and 1.5 times with a variable-speed drive. Motors are assumed to start one at a time.
- Required size: the larger of the running load plus the safety margin, and the peak while the largest motor starts.
- Generator sets are rated at power factor 0.8, so kVA = kW ÷ 0.8.